©2013 Magnum Energy, Inc. 14
3.0 Setup
MM, MM-AE and MMS Series (and any export version of these
models): These models do not monitor current on the input, therefore
cannot bene t from the Shore Max setting or feature. On these models, the
Shore Max setting may be displayed and allow selection/adjustment, but will
not do anything to reduce the battery charger current.
3.3.2 AGS Menu
The AGS button allows an optional Auto Generator Start – Network (AGS-N)
controller (if installed and networked) to be con gured to your speci c
system preferences, and enables you to check the status of the AGS.
Info: Refer to Section 7.0 (in this manual) and to your ME-AGS-N
Owner’s Manual (PN: 64-0039) for detailed information on the AGS.
AGSSHORE
METER SETUP
TECH
Status...
01 AGS Control
Press
Figure 3-4, AGS Menu Display
3.3.3 METER Menu
Pressing the METER button accesses the various meters that assist in
determining the status of the inverter/charger and the battery system.
Info: All displays revert back to the home screen (except for the
displays under the METER button) if no button has been pressed
for approximately ve minutes.
METER: 01 INV/CHG Meter – This menu item displays the DC voltage
and current while either inverting or charging.
DC: V (Volts) & A (Amps): First value displays the voltage from the
batteries connected to the inverter. This reading’s accuracy is ±1.5%
with a 0.1 VDC resolution. Second value displays (while inverting) a
negative number to show the battery current used by the inverter. If
charging, the DC: A (Amps) reading displays a positive number to show
the amount of current delivered to the batteries. The accuracy of this
display below 1 amp AC (~10 amps DC @ 12VDC) is not detected. When
the current into or out of the batteries is greater than 1 amp AC, the
display accuracy is ±20%.
VAC Out: Display provides the AC voltage measurement at the inverter’s
output terminals. If inverting, this measures the inverter’s output
voltage. When in Standby mode, this measures the AC voltage that is
passing through the inverter from the source (e.g., grid or generator).
Hz Out: Displays (while inverting) the output frequency of the inverter.
When in Standby mode, this meter displays the frequency of the
incoming AC source (i.e., grid or generator) that is passing through the
inverter to the inverter’s output terminals. Frequency in Hertz (Hz).
Load Amps: Displays the AC amps as measured on the inverter’s AC
output terminals. The reading is positive (+) if power is being pulled