11 ©2013 Magnum Energy, Inc.
3.0 Setup
Table 3-1, ME-RC Compatibility Matrix (cont.)
Button
FEATURES/SETTINGS
Model/
Level
Required
Default
Setting
Main
Menu
Menu
Heading/Item
Selections/
Adjustments Range
SETUP
01 Search
Watts
Search= OFF, 5-50W ≥Level 1 5W
02 Low
Batt Cut-
Out
LBCO= 9.0-12.2 VDC* ≥Level 1
10.0
VDC
03 Absorb
Time
Absorb Hrs= 0.0-25.5 Hrs
≥Level 4
[4]
1.5 Hrs
04 Battery
Type
BatType=
Gel, Flooded, AGM1, AGM2 ≥Level 1 Flooded
Custom
[2]
Absorb=
(12.0-16.0V)*
≥Level 3
14.4V
Float=
(12.0-16.0V)*
13.2V
Equalize=
(12.0-16.0V)*
15.6V
05 Charge
Rate
Max Charge=
0-100% ≥Level 3
80%
10-100% ≥Level 2
06 VAC
Dropout
Dropout=
US Models: 60-100 VAC,
UPS Mode
≥Level 1 80 VAC
Export Models: 110-190
VAC, UPS Mode
≥Level 1 150 VAC
07 Power
Save
PwrSave= OFF, 1-60 Minutes ≥Level 1 15min
08 Screen
Setup
Contrast=
0-100% ≥Level 1
100%**
Brightness= 50%**
09 Final
Charge
Final=
Multi, Float, Silent
≥Level 4
[5]
Multi
Silent
Rebulk=
(12.0-16.0V)*
12.0V
10 Pwr Up
Always
Pwr Up= YES, NO ≥Level 1 NO
TECH
01 Tem-
peratures
BTS:
Read only displays ≥Level 1
Read
Only
Tfmr:
FETs:
AGS:
02 Revi-
sions
Inverter:
Read only displays ≥Level 1
Read
Only
Remote:
AGS:
BMK:
Router:
Commentaires sur ces manuels