3.0 Setup
Battery
Type
Inverter
Voltage
Absorption
Voltage
Float
Voltage
Equalization
Voltage
GEL
12 VDC 14.1 VDC 13.6 VDC 14.1 VDC
1
24 VDC 28.2 VDC 27.2 VDC 28.2 VDC
1
48 VDC 56.4 VDC 54.4 VDC 56.4 VDC
1
Flooded
12 VDC 14.6 VDC 13.4 VDC 15.5 VDC
24 VDC 29.2 VDC 26.8 VDC 31.0 VDC
48 VDC 58.4 VDC 53.6 VDC 62.0 VDC
AGM 1
2
12 VDC 14.3 VDC 13.1 VDC 15.5 VDC
24 VDC 28.6 VDC 26.2 VDC 31.0 VDC
48 VDC 57.2 VDC 52.4 VDC 62.0 VDC
AGM 2
3
12 VDC 14.5 VDC 13.5 VDC 14.5 VDC
1
24 VDC 29.0 VDC 27.0 VDC 29.0 VDC
1
48 VDC 58.0 VDC 54.0 VDC 58.0 VDC
1
Custom
4
12 VDC 12.0-16.0 VDC 12.0-16.0 VDC 12.0-16.0 VDC
24 VDC 24.0-32.0 VDC 24.0-32.0 VDC 24.0-32.0 VDC
48 VDC 48.0-64.0 VDC 48.0-64.0 VDC 48.0-64.0 VDC
Note¹: Voltage same as Absorption Voltage—to prevent equalization.
Note²: Speci cations for Concord (Lifeline Series) AGM batteries.
Note³: Speci cations for East Penn, Deka, Discover and Trojan AGM batteries.
Note: When using the Custom setting, the EQ (Equalization) voltage adjustment
cannot be set lower than the Absorb Voltage setting. Also, the EQ voltage
adjustment cannot be set higher than 2-volts (12V systems), 4-volts (24V
systems), or 8-volts (48V systems) above the Absorb Voltage setting.
Table 3-4, Battery Type to Charge Voltages
Info: The voltage settings in Table 3-4 are based on the Battery
Temperature Sensor (BTS) at a temperature of 77° F (25° C), or
the BTS not connected. If the BTS is connected, the actual charge
voltage will increase if the temperature around the BTS is below
77° F (25° C), and decrease if higher than 77° F (25° C). This en-
sures the batteries receive the correct charge voltage regardless
of temperature.
Press to save
SETUP
Press
Status...
04 Battery Type
Rotate to
Press to select
Rotate to
desired
selection:
Status...
BatType=GEL
Status...
BatType=AGM1
Status...
BatType=Custom
Status...
BatType=Flooded
....
Figure 3-9, SETUP: 04 Battery Type Selections