Page 1 - Standard Remote Control

Owner’s Manual(Revision 2.7 or higher: includes AGS & BMK info)ME-RCStandard Remote Control

Page 2

3 ©2013 Magnum Energy, Inc.2.0 Installation Figure 2-2, Remote Control ConnectionsFigure 2-1, Remote Cable2.2 Connecting the Remote CableThe ME-RC c

Page 3 - Product Safety Alerts

©2013 Magnum Energy, Inc. 42.0 InstallationFigure 2-3, ME-RC Remote Dimensions2.3 ME-RC Remote DimensionsUse the information below (Figures 2-3 and

Page 4 - Table of Contents

5 ©2013 Magnum Energy, Inc.2.0 Installation Figure 2-4, Flush Mounting the ME-RC3.0"(7.6 cm)5.0"(12.7 cm)2.4.1 Flush Mount Installation Pr

Page 5 - Table of Contents (Cont.)

©2013 Magnum Energy, Inc. 6FAULTPWRCHGINVInvertingDC 25.2V - 10A Top line: Current status of inverterBottom line: Voltage from the batteries conn

Page 6 - List of Figures

7 ©2013 Magnum Energy, Inc.3.0 Setup 3.0 SetupWhen the remote is connected to a Magnum inverter/charger, the settings in the remote control determine

Page 7 - List of Figures (Cont.)

©2013 Magnum Energy, Inc. 83.0 SetupFigure 3-2, SETUP Menu NavigationInvertingBatType=Flooded4. Press the SELECT knob to change the desired setting.B

Page 8 - 1.0 Introduction

9 ©2013 Magnum Energy, Inc.3.0 Setup 3.2 Remote Feature to Inverter CompatibilityThe ME-RC has many settings and is designed to work with the standa

Page 9

©2013 Magnum Energy, Inc. 103.0 SetupButtonFEATURES/SETTINGSInverter Model/LevelRequiredDefault SettingMenuHeadingMenu ItemSelections/Adjustments Ran

Page 10 - 2.0 Installation

11 ©2013 Magnum Energy, Inc.3.0 Setup Table 3-1, ME-RC Compatibility Matrix (cont.)ButtonFEATURES/SETTINGSModel/LevelRequiredDefault SettingMain Menu

Page 11

©2013 Magnum Energy, Inc. 123.0 Setup3.3 Remote Buttons and Menu ItemsThe fi ve menu pushbuttons (SHORE, AGS, METER, SETUP, or TECH) allow the invert

Page 12 - (12.7 cm)

i ©2013 Magnum Energy, Inc.Disclaimer of LiabilitySince the use of this manual and the conditions or methods of installation, operation, use and main

Page 13 - DC 25.2V - 10A

13 ©2013 Magnum Energy, Inc.3.0 Setup Press to savePressSHORERotate to desired selection: Status...Shore Max = 5ABottom line shows current saved sett

Page 14 - 3.0 Setup

©2013 Magnum Energy, Inc. 143.0 SetupMM, MM-AE and MMS Series (and any export version of these models): These models do not monitor current on the in

Page 15 - ©2013 Magnum Energy, Inc. 8

15 ©2013 Magnum Energy, Inc.3.0 Setup 3.3.4 SETUP MenuPressing the SETUP menu button provides access to the menu items and settings that allow the in

Page 16

©2013 Magnum Energy, Inc. 163.0 SetupPress to saveSETUPPressStatus...01 Search WattsRotate toPress to selectRotate to desired selection: Status...

Page 17 - ©2013 Magnum Energy, Inc. 10

17 ©2013 Magnum Energy, Inc.3.0 Setup • SETUP: 03 Absorb Time – Used to determine when the charger completes the Absorption stage and transitions to

Page 18 - 11 ©2013 Magnum Energy, Inc

©2013 Magnum Energy, Inc. 183.0 SetupPress to saveSETUPPressStatus...03 Absorb TimeRotate toPress to selectRotate to desired selection: Status... Abs

Page 19 - 3.3.1 SHORE Menu

19 ©2013 Magnum Energy, Inc.3.0 Setup Group/Code SizePhysical Size (L” x W” x H”)Battery VoltageBattery AHrs (20-hr rate)GC-2 (Golf cart) 10 3/8 x 7

Page 20

©2013 Magnum Energy, Inc. 203.0 SetupBattery TypeInverter VoltageAbsorption VoltageFloatVoltageEqualization VoltageGEL12 VDC 14.1 VDC 13.6 VDC 14.1 V

Page 21 - 01 AGS Control

21 ©2013 Magnum Energy, Inc.3.0 Setup Where should I set my Maximum Charge Rate? The maximum charge rate is generally set to a C/5* rate (C = the tot

Page 22

©2013 Magnum Energy, Inc. 223.0 Setup• SETUP: 06 VAC Dropout – Used to select the minimum AC voltage that must be present on the input before the in

Page 23

©2013 Magnum Energy, Inc. iiImportant Product Safety InstructionsThis manual contains safety instructions that must be followed during the installati

Page 24

23 ©2013 Magnum Energy, Inc.3.0 Setup • SETUP: 08 Screen Setup – Used to adjust the contrast of the LCD screen and the backlight brightness for the

Page 25

©2013 Magnum Energy, Inc. 243.0 Setup• SETUP: 09 Final Charge – The Final Charge stage setting is the stage to which the charger will transition aft

Page 26

25 ©2013 Magnum Energy, Inc.3.0 Setup 3.3.5 TECH MenuThe TECH menu button provides access to selections that are used to assist service technicians i

Page 27

©2013 Magnum Energy, Inc. 263.0 SetupTECHPressStatus...01 TemperaturesRotate toPress to selectRotate to desired display: Status... BTS: ##C/ ##F

Page 28

27 ©2013 Magnum Energy, Inc.3.0 Setup • TECH: 04 Load Defaults – This menu restores all settings on the inverter/charger, and any settings on access

Page 29

©2013 Magnum Energy, Inc. 283.0 SetupTECHPressStatus...05 Ext ControlRotate toPress to selectRotate to desired display: Status... Shore Max: EXT

Page 30

29 ©2013 Magnum Energy, Inc.3.0 Setup Entering an Existing PINWhen entering a menu (or pressing the SETUP button) the “PIN = 0***” menu displays. The

Page 31

©2013 Magnum Energy, Inc. 304.0 Menu MapFigure 4-1, Inverter/Charger Menu MapAGSRefer to Section 7.0 in this manual and to the ME-AGS-N Owner’s Manua

Page 32

31 ©2013 Magnum Energy, Inc.4.0 Menu MapFigure 4-2, Inverter/Charger Menu MapSETUPcontinued…...* LBCO settings are dependent on inverter model (valu

Page 33

©2013 Magnum Energy, Inc. 324.0 Menu MapSETUPcontinued…...Status...08 Screen SetupStatus...Contrast = 0%Status...Contrast = 10%Status...Contrast

Page 34

iii ©2013 Magnum Energy, Inc.Table of Contents1.0 Introduction ...12.0 Installation ...

Page 35

33 ©2013 Magnum Energy, Inc.4.0 Menu MapStatus...04 Load DefaultsStatus...Defaults in 4.9Status...DEFAULTS LOADEDStatus...03 Inv ModelStatus...Model:

Page 36

©2013 Magnum Energy, Inc. 345.0 Operation5.0 OperationThis section explains how to operate the inverter/charger using the ME-RC remote. It also provi

Page 37 - Read Only displays

35 ©2013 Magnum Energy, Inc.5.0 Operation5.1.3 ON/OFF Pushbuttons• ON/OFF INVERTER – This button toggles the inverter function on and off. The green

Page 38 - 4.0 Menu Map

©2013 Magnum Energy, Inc. 365.0 Operation5.2 Operating the Inverter/Charger5.2.1 Inverter ModeTurning the inverter on: Press the ON/OFF INVERTER but

Page 39

37 ©2013 Magnum Energy, Inc.5.0 OperationThere are three operating modes of the inverter/charger:• Inverter mode • Charger mode • Fault

Page 40

©2013 Magnum Energy, Inc. 385.0 Operation5.3.2 Charger Mode Status MessagesWhen AC power (utility or generator) is connected to the inverter/charger

Page 41 - 5.0 Operation

39 ©2013 Magnum Energy, Inc.5.0 OperationCharger Standby appears on LCD. PWR (green) LED is on solid and CHG (green) LED slowly blinks. FAULT (red) L

Page 42

©2013 Magnum Energy, Inc. 405.0 Operation• Equalizing – The battery charger is delivering the equalize voltage to the batteries; see Table 3-4 to det

Page 43

41 ©2013 Magnum Energy, Inc.5.0 OperationFull Charge appears on LCD. PWR (green) LED is on solid, and CHG (green) LED blinks slowly. FAULT (red) LED

Page 44 - Inverter Standby

©2013 Magnum Energy, Inc. 425.0 OperationLoad Support VDC appears on LCD. PWR (green) LED is on solid, and CHG (green) LED blinks slowly. FAULT (red)

Page 45 - Searching

©2013 Magnum Energy, Inc. ivTablesTable 3-1, ME-RC (Revision 2.7) Compatibility Matrix ... 9Table 3-2, Battery AmpHrs Capac

Page 46 - Bulk Charging

43 ©2013 Magnum Energy, Inc.5.0 OperationAC Backfeed appears on the LCD. The FAULT (red) LED is on. The PWR (green), CHG (green), and INV (green) LED

Page 47 - Equalizing

©2013 Magnum Energy, Inc. 445.0 OperationBreaker Tripped appears on the LCD. The FAULT (red) LED is on. The PWR (green), CHG (green), and INV (green)

Page 48

45 ©2013 Magnum Energy, Inc.5.0 OperationInfo: The HBCO value is dependent on your inverter revision and model. Normally, the HBCO value for ME/MM/RD

Page 49 - Load Support VDC

©2013 Magnum Energy, Inc. 465.0 OperationHigh Volts AC appears on the LCD.The FAULT (red) LED is on. The PWR (green), CHG (green), and INV (green) LE

Page 50 - AC Overload

47 ©2013 Magnum Energy, Inc.5.0 Operation• Overtemp – The inverter/charger has shut down because the internal power components (FETs and/or Transform

Page 51 - Breaker Tripped

©2013 Magnum Energy, Inc. 485.0 OperationTfmr Overtemp appears on the LCD. The FAULT (red) LED is on. The PWR (green), CHG (green), and INV (green) L

Page 52 - High Battery

49 ©2013 Magnum Energy, Inc.5.0 OperationStack Mode Fault appears on the LCD. The FAULT (red) LED is on. The PWR (green), CHG (green), and INV (green

Page 53

©2013 Magnum Energy, Inc. 505.0 Operation5.3.3.3 Internal Fault MessagesThe inverter continually monitors several internal components and will shut

Page 54

51 ©2013 Magnum Energy, Inc.5.0 OperationLED Status MeaningPWR (green)OFF1. Inverter is disabled; 2. Remote is in Power Saver mode – press any button

Page 55 - Tfmr Overtemp

©2013 Magnum Energy, Inc. 526.0 Troubleshooting6.0 ME-RC Remote TroubleshootingThe remote may not be functioning correctly, use the following table

Page 56

v ©2013 Magnum Energy, Inc.List of FiguresFigure 1-1, Front Panel Features ... 1Figure 2-1, Re

Page 57 - Internal NTC

53 ©2013 Magnum Energy, Inc.6.0 Troubleshooting6.1 Inverter/Charger Troubleshooting Tips6.1.1 Inverter Problems• Inverter turned on, green INV LED

Page 58

©2013 Magnum Energy, Inc. 546.0 Troubleshooting6.2 Performing an Inverter ResetTo perform an inverter reset (i.e., “soft reset”): 1. Remove all AC

Page 59 - 6.0 Troubleshooting

7.0 Using an AGS Module55 ©2013 Magnum Energy, Inc.7.0 Using a ME-AGS-N ModuleThe ME-RC remote’s AGS menus under the AGS and TECH buttons allow you

Page 60

©2013 Magnum Energy, Inc. 56AGS: 03 Run Time Hour MenuThis menu provides the settings that determine the length of time the generator will run once i

Page 61 - 6.3 Performing a Power Reset

7.0 Using an AGS Module57 ©2013 Magnum Energy, Inc.sensor (or thermostat control) reading is above the AGS: 04 Start Temp F setting, the generator w

Page 62 - 7.0 Using a ME-AGS-N Module

©2013 Magnum Energy, Inc. 58Info: The default settings and range are automatically determined based on the connected inverter and the measured VDC.Wh

Page 63 - 7.0 Using an AGS Module

7.0 Using an AGS Module59 ©2013 Magnum Energy, Inc.7.2 AGS Functional TestsOnce you establish all the autostart/autostop settings you need, perform

Page 64

©2013 Magnum Energy, Inc. 60• Enable – Select this option to have the AGS monitor temperature (04 Start Temp F) and/or the inverter’s battery voltage

Page 65

7.0 Using an AGS Module61 ©2013 Magnum Energy, Inc.Info: When the RV mode is used and the AGS system feature is required, the user will need to re-en

Page 66 - 7.3 AGS Operation/Monitoring

©2013 Magnum Energy, Inc. 62To manually stop the generator (only if autostarted by AGS):1. Press the AGS button. The 01 AGS Control menu displays.2.

Page 67

©2013 Magnum Energy, Inc. viList of Figures (Cont.)Figure 5-13, Full Charge Mode ... 41Figure

Page 68

7.0 Using an AGS Module63 ©2013 Magnum Energy, Inc.AGSStatus...01 AGS ControlStatus... AGS= OFF Status... AGS= EnableStatus...AGS=

Page 69

©2013 Magnum Energy, Inc. 64Figure 7-3, AGS Menu Maps in ME-RC Remote (Section 2)TECHRead Only displaysStatus...01 TemperaturesStatus... AGS: ##C

Page 70

7.0 Using an AGS Module65 ©2013 Magnum Energy, Inc.7.7 ME-AGS-N Remote Status MessagesA status message may be an operational or a fault message. Acc

Page 71

©2013 Magnum Energy, Inc. 667.7.2 AGS Remote Start StatusesThe following “Start” statuses identify the condition that autostarted the generator. If

Page 72

7.0 Using an AGS Module67 ©2013 Magnum Energy, Inc.Figure 7-4, Example: AGS Fault Message on ME-RC Remotestarts or until all its start attempts are r

Page 73

©2013 Magnum Energy, Inc. 687.0 Using an AGS Module7.8.2 Resolving Operational StatusesThe following operational statuses can display on your remote

Page 74 - Inverter/Charger Setting/Info

7.0 Using an AGS Module69 ©2013 Magnum Energy, Inc.Fault Gen Run – The generator successfully started and ran for more than two minutes, but the gene

Page 75

©2013 Magnum Energy, Inc. 708.0 Using a ME-BMKThis section discusses how to set up and operate the BMK using the ME-RC50 remote. It also shows what

Page 76

8.0 Using a BMK71 ©2013 Magnum Energy, Inc.press to saveMETERpress Status... 05 BM: Setuprotate topress to select (press x2 for ME-RC50's with R

Page 77 - 8.0 Using a ME-BMK

©2013 Magnum Energy, Inc. 728.3 ME-RC50 Remote’s BMK METER Menu MapsThe diagram below is a complete overview of the battery monitor settings and inf

Page 78 - 8.0 Using a BMK

1 ©2013 Magnum Energy, Inc.1.0 Information 1.0 IntroductionThe ME-RC remote control allows you to monitor and customize the operating parameters for

Page 79

8.0 Using a BMK73 ©2013 Magnum Energy, Inc.8.4.1 How the Battery Monitor (ME-BMK) OperatesThe ME-BMK battery monitor uses a precision resistor known

Page 80

©2013 Magnum Energy, Inc. 74point. While this reference point is being calculated, the display will show “Think’n”, to indicate that the SOC referenc

Page 81

8.0 Using a BMK75 ©2013 Magnum Energy, Inc.• tAH Out (Total AHrs Removed) – This meter displays the total AHrs removed from the battery since the Sen

Page 82

©2013 Magnum Energy, Inc. 769.0 Service and Warranty Info9.0 Service and Warranty InfoMagnum Energy, Inc., (hereafter “Magnum”) warrants the ME-RC r

Page 83 - 9.0 Service and Warranty Info

Magnum Energy, Inc.2211 West Casino RdEverett, WA 98204Phone: 425-353-8833Fax: 425-353-8390Web: www.magnumenergy.comPN: 64-0003 Rev F

Page 84 - PN: 64-0003 Rev F

©2013 Magnum Energy, Inc. 22.0 Installation2.0 InstallationReview this section and the Important Product Safety Instructions on page ii before procee